IO ActiveX Interface

Home Page

Communications

MAIN FUNCTIONS:
Open(PortName, Setup)    Added TCP support (Rev 2.01 and Greater)
Close()
WriteString(Data)
ReadString(Length)
WriteByte(Data)
ReadByte()
SetTimeOut(Time)
SetTimeOuts(BaseTime, Multiplier)
SetHandshaking(HSMethod)
WriteData(Data, Length)
ReadData(Length)
ReadTil(EndStr, EndStrLen, TimeOut, Length)   New (Rev 2.01 and Greater)
 

ADDITIONAL FUNCTIONS:
BytesRead()
ListPorts(Index, Type)
NumberRetries(Retries)
DataBuffer
Mode
GetLastJobSubmitted
GetLastJobCompleted
PortName
NumBytesRead
NumBytesWritten
GetPortHandle()
SetBufferSize(InSize, OutSize)
Sleep()
Wait()
OpenEx()
CancelIO()
GetInfoInt(InfoID)New (Rev 2.01 and Greater)
GetInfoString(InfoID)New (Rev 2.01 and Greater)
WriteBytes(ByteArray)New (Rev 2.03 and Greater)
ReadBytes(ByteArray, Length)   New (Rev 2.03 and Greater)

Status

ParallelStatus
SerialStatus
TCPStatus
NumCharsInQue
NumCharsOutQue

 
Communications Events

IOStatusEvent(StatusType, IOStatus)
IOCompleteEvent(JobType, JobId, JobResult)
IOQueueEvent(NumCharsInputQue, NumCharsOutputQue)
IOPeriodicEvent()

StatusEventInterval
PeriodicEventEnabled
 

Parallel Specific

InitPrinter()
Out()   Modified to work on NT4.0, Win2000, WinXP (Rev 2.01 and Greater)
In()      Modified to work on NT4.0, Win2000, WinXP (Rev 2.01 and Greater)
DeviceControl()
 

Serial Specific

SerialPortSetupDialog()
SerialSetPortDefaults()
SerialGetPortDefaults()
SerialBreak()
SerialSetBaud(BaudRate)New (Rev 2.01 and Greater)
 

Serial Specific (Advanced)

SerialCTSFlow(Value)
SerialDSRFlow(Value)
SerialDTRControl(long Value)
SerialDSRSensitivity(Value)
SerialTxContinueOnXoff(Value)
SerialOutX(Value)
SerialInX(Value)
SerialErrorReplacment(Value)
SerialNullStripping(Value)
SerialRTSControl(Value)
SerialXonLimit(Value)
SerialXoffLimit(Value)
SerialXonCharacter(Value)
SerialXoffCharacter(Value)
SerialErrorCharacter(Value)
SerialEndCharacter(Value)


 
 


Open(PortName, Setup)

 
Parameters
PortName is the name of the port to be opened. Non standard port names and ports higher than 9, may need to be prefixed with "\\.\" and have no trailing ':' (in C/C++ "\\\\.\\").
Setup is a string that will set the mode of operation for a serial port. Not used with parallel ports.

Remarks
Opens a port for doing input and output.
If you are doing TCP communications, the server connection must be opened first then the client TCP connection.

Returns
1 if successful and 0 if the function fails.
2 if successful but the port setup fails. This can happen when another app/driver is using the port.
 

Example
Result = IO1.Open("LPT1:", "") 'Open a parallel Port.
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
Result = IO1.Open("\\.\digi1", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
Result = IO1.Open("\\.\COM22", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
Result = IO1.Open("localhost:9092", "server") 'Open a TCP Port 9092.
Result = IO1.Open("localhost:9092", "client") 'Open a TCP Port 9092.
Result = IO1.Open("192.168.1.5:9092", "client") 'Open a TCP Port 9092.

NOTE: On Win NT Open() can fail if another device/driver is setup to use the port you are trying to open. Remove all devices/drivers setup to use this port, including printer drivers.

NOTE (TCP):
From the server end-
IO1.Open localhost : Port, "server"

From the client end:
IO1.Open remotehost : Port, "client"

where:
1: the server end is opened first
2: "localhost" at the server end is the same "remotehost" at the client end
3: Monitor IOstatusevent. If any of the 2 ends is closed, the other end must be subsequently closed before attempting to open a line using the same IP address and Port numbers.

If "reconnect" (i.e. "server reconnect") is specified in the setup string, the IO control will attempt to automatically reconnect a lost connection.
 
 
 


Close()  
Parameters
None.

Remarks
Closes an open port.

Returns
1 if successful and 0 if the function fails.

Example
Result = IO1.Close()
 
 
 
 


WriteString(Data)  
Parameters
Data Thestring to be written

Remarks
Writes a string to the previously opened port. For binary data  (i.e. Nulls) use the WriteData function. If the function fails, you may need to increase the timeout value via SetTimeOuts.  On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a write.

Returns
1 if successful and a 0 if the function fails.

Example
Result = IO1.WriteString("Hello World" + Chr(13) + Chr(10)) 'Sends "Hello World" to a printer or other device.

Note: On PC's setup for countries such as Chinese, Japanese, or other symbol type languages, you may have to use the ReadBytes() and WriteBytes() functions to avoid unwanted Unicode character translation.
 
 


ReadString(Length)  
Parameters
Length The number of characters to read from the port.

Remarks
Reads characters from an opened port and returns them as a string. For binary data (i.e. Nulls) use the function ReadData. When reading data from a parallel port, this function uses the RS1284 protocol for reading data from the parallel port. If the function fails, you may need to increase the timeout value via SetTimeOuts.  On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a read.

Example
String = IO1.ReadString(30) 'Reads data from a port. Typically a request for data precedes this command.
 

Note: On PC's setup for countries such as Chinese, Japanese, or other symbol type languages, you may have to use the ReadBytes() and WriteBytes() functions to avoid unwanted Unicode character translation.
 
 



 

WriteByte(Data)

 
Parameters
Data The byte/character to be written

Remarks
Writes a byte/character to the previously opened port. If the function fails, you may need to increase the timeout value via SetTimeOuts.  On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a write.

Returns
1 if successful and a 0 if the function fails.

Example
Result = IO1.WriteByte(10) 'Sends Line feed to a printer or other device.
 
 
 


ReadByte()  
Parameters
None.

Remarks
Reads a byte/character from an opened port. When reading data from a parallel port, this function uses the RS1284 protocol for reading data from the parallel port. This function returns the byte data in an integer. Some environments my sign extend this value. You may wish to do a bitwise AND with the value read from this function and a hex FF to restore it to an unsigned value.  On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus()routine before you do a read.

Returns
The byte/character.

Example
Result = IO1.ReadByte() 'Reads 1 data byte from a port. Typically a request for data precedes this command.
  OR
Result = IO1.ReadByte() And &Hff 'restores to unsigned byte
 
 
 
 

SetTimeOut(Time)  
Parameters
Time The base time in milliseconds. For Reading a port the timeout will be: Time + (number of characters to read) x Time .For writing to a port the time out will be: Time + (number of characters to write) x Time. A value of zero indicates that timeout are not used. Default timeout factor is 20.

Remarks
Sets the time out factor for a port. The write/read operation will be tried until the time is expired. If the timeout expires, the function will return an error (0) result.

Returns
1 if successful and a 0 if the function fails. If you call this function before the port is opened, it will return 0. In this case the information will be retained untill the port is opened and applied at that time.

Example
Result = IO1.SetTimeOut(20) 'Sets timeout factor, how long a request is tried before an error is returned.
 


 

SetTimeOuts(BaseTime, Multiplier)

 
Parameters
BaseTime The base time in milliseconds.
Multiplier The multiplication time in milliseconds.
 

Remarks
Sets the time out factor for a port. The write/read operation will be tried until the time is expired. If the timeout expires, the function will return an error (0) result.  For Reading a port the timeout will be: BaseTime + (number of characters to read) x Multiplier .For writing to a port the time out will be: BaseTime + (number of characters to write) x Multiplier.

BaseTime + (number of characters to read) x Multiplier.  Where "BaseTime" is the minimum time out regardless of how many characters are communicated and the "Multiplier" time is multiplied with the string length and these two times are added together to get the total time out.
 

Returns
1 if successful and a 0 if the function fails. If you call this function before the port is opened, it will return 0. In this case the information will be retained untill the port is opened and applied at that time.

Example
Result = IO1.SetTimeOut(200, 20) 'Sets timeout factor, how long a request is tried before an error is returned.
 
 
 
 
 


 

SetHandshaking(HSMethod)

 
Parameters
HSMethod The type of handshaking protocol to be used with a serial port. 'Serial ports Only. 0 = None, 1 = Xon/Xoff, 2 = Hardware

Remarks
Sets the type of handshaking to be used with this port, the device must be configured to use the same type of handshaking protocol.  Calling this function will reset the baud rate, parity, and stop bits to the values passed into the Open() function.  This function should be called before the "Advanced Serial Communications" functions.  SetHandshaking() will cancel the "Advanced Serial Communications" functions settings.

Returns
1 if successful and a 0 if the function fails. If you call this function before the port is opened, it will return 0. In this case the information will be retained untill the port is opened and applied at that time.

Example
Result = IO1.SetHandshaking(2) 'Serial ports Only. 0 = None, 1 = Xon/Xoff, 2 = Hardware
 
 
 
 
 
 


WriteData(Data, Length)  
Parameters
Data The binary data to be written, can include embedded nulls.
Length The length of data to be written.

Remarks
Writes data to the previously opened port. If the function fails, you may need to increase the timeout value via SetTimeOuts. On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a write.

Returns
The length of data written if successful and a 0 if the function fails.

Example
Result = IO1.WriteData("String1" + Chr(00) + "String2" + Chr(00) + "String3" + Chr(00) + Chr(00)) 'Sends 3 null terminated strings to the port, with the total data being double null terminated.
 

Note: On PC's setup for countries such as Chinese, Japanese, or other symbol type languages, you may have to use the ReadBytes() and WriteBytes() functions to avoid unwanted Unicode character translation.
 
 


ReadData(Length)  
Parameters
Length The number of bytes to read from the port.

Remarks
Reads bytes from an opened port and returns them in a string. The data can have null bytes. Even thought this function will return a string with embedded nulls other functions that operate on strings may not be null friendly. When reading data from a parallel port, this function uses the RS1284 protocol for reading data from the parallel port. On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a read.

Returns
Binary data in a string.

Example
String = IO1.ReadData(30) 'Reads data from a port. Typically a request for data precedes this command.

Note: On PC's setup for countries such as Chinese, Japanese, or other symbol type languages, you may have to use the ReadBytes() and WriteBytes() functions to avoid unwanted Unicode character translation.
 


 
 


ReadTil(EndStr, EndStrLen, Timeout, AbortLength)

 
Parameters
EndStr Is a string that when read will cause the function to return.
EndStrLen Is the length of EndStr.
Timeout The minimum time in milliseconds that the function will wait for the "END" string to arrive.
AbortLength The max number of bytes to read from the port.

Remarks
Reads bytes from an opened port and returns them in a string. The data can have null bytes. Even thought this function will return a string with embedded nulls other functions that operate on strings may not be null friendly. When reading data from a parallel port, this function uses the RS1284 protocol for reading data from the parallel port. On a NT PC you should check to see if the parallel device is on-line via the ParallelStatus() routine before you do a read.

Returns
Binary data in a string.

Example
String = IO1.ReadTil(Chr(13)+Chr(10), 2, 3000, 50) 'Reads data from a port. Typically a request for data precedes this command.
 
 
 


BytesRead()  
Parameters
None.

Remarks
Return the number of bytes previously read from the port. This value corresponds to the last read function done on this port. For use with the ReadData() function.

Returns
The number of bytes previously read function called.

Example
String = IO1.ReadData(30) 'Reads data from a port.
NumBytes = IO1.BytesRead() 'returns number of bytes read.
 
 
 
 
 


ListPorts(Index, Type)  
Parameters
Index The nth item in the list to retrieve.
Type The type of port to be retrieve.

Remarks
Type is 1 for COM ports, 2 for LPT ports and, 4 for all ports. Note you can OR these values together to get a combination.

Returns
Returns the ports availble on the machine for the given index.

Example
For i = 0 To 10
Label2.Caption = Label2.Caption + IO1.ListPorts(i, 1) + " "
Next i
 
 
 
 


NumberRetries(Retries)  
Parameters
Retries The number of times an I/O operation will be tried before a failure is returned.

Remarks
Default is 1 retry.

Returns
Returns 1.

Example
Result = IO1.NumberRetries(1)
 
 
 
 

DataBuffer (Property) R Remarks
This buffer reflects the last read data. It is typically used during a IOCompleteEvent when a background read is completed. It's contents are not valid until a read has beed done (ie. ReadString or ReadData).
Mode (Property) R/W Remarks
Set this to 0 (MODE_NORMAL) for normal operation, or to 2 (MODE_ASYNC) for background I/O operations.   In the background (or asynchronous) mode of operation, the IO control will perform read and write operations on a background process. Write operations will set a "Job ID" number. This number can be obtained by calling GetLastJobSubmitted(). When the operation is complete, an IOComplete event will be fired signaling the completion of the operation and the result of the operation. This background operation will allow slow I/O operations to be done and not tie up the main application.  When a background read function finishes the data will be in DataBuffer.

If using 2 (MODE_ASYNC), set the Mode after you Open() the communications port. The background I/O operations work for ReadString() and WriteString() and ReadData() and WriteData() also.  But, not for ReadByte() and WriteByte().  You can have more than one write data function outstanding (queued in order), but typically only one read data function is pending at a time.
 
 

GetLastJobSubmitted()
 
Remarks
Returns the "Job ID" for the last submitted background job (read or write).  (i.e. Mode = 2 (MODE_ASYNC))


GetLastJobCompleted()
 

Remarks
Returns the "Job ID" for the last job completed by a background job (read or write).  (i.e. Mode = 2 (MODE_ASYNC))

 
 
 

PortName (Property) R

Remarks
PortName reflects the name of the open port. This is provided for the convience of the application, the application upon detecting an error condition can use PortName to display a message to the application user to take corrective action.

 
 

NumBytesRead (Property) R

Remarks
This reflects the number of byte/characters read during the last read operation.

 

NumBytesWritten (Property) R

 
Remarks
This reflects the number of byte/characters write during the last write operation.
GetPortHandle()  
Parameters
None .

Remarks
This function returns the handle of the currently opened port. This function is provided to allow calls to the Windows API directly.

Returns
The handle of the currently opened port.

Example
Result = IO1.GetPortHandle()
 


 
 

SetBufferSize(InSize, OutSize)

 
Parameters
InSize. Specifies the size of the input buffer.
OutSize. Specifies the size of the output buffer.

Remarks
This function sets the size of the input and output buffer associated with the opened port. Caution should be taken when using this function, some hardware running Windows 95 can function incorrectly when overriding the default buffer size with a serial port.

Returns
0 if the function fails.

Example
Result = IO1.SetbufferSize(InSize, OutSize)
 
 

Sleep(NumMilliseconds)  
Parameters
NumMilliseconds. Specifies the length of the delay produced by calling this function.

Remarks
This function delays for the number of milliseconds specified. This function is provided to allow for custom timing of signals on the ports.
 

Returns
None.

Example
IO1.Sleep(500) ‘delay for 500ms (½ second).
 
 


 

Wait(NumMilliseconds)

 
Parameters
NumMilliseconds. Specifies the minimum length of the delay produced by calling this function.

Remarks
This function delays for the number of milliseconds specified. This function differs from Sleep() in that it will yield the current thread to allow the application to process user input.  This yielding lets the application respond to user input instead of appearing to "hang" during a long delay.  Because this functions yields to other tasks, it may delay for longer than the time specified.
 

Returns
None.

Example
IO1.Wait(500) ‘delay for at least 500ms (½ second).
 
 


OpenEx(PortName, Setup, Mode, Extra)

 
Parameters
PortName is the name of the port to be opened. Non standard port names and ports higher than 9, may need to be prefixed with "\\.\" and have no trailing ':' (in C/C++ "\\\\.\\").
Setup is a string that will set the mode of operation for a serial port. Not used with parallel ports.
Mode is the extra mode parameter dictating how the open is done: OPEN_MODE_NORMAL     (0)        Extra = Not used
OPEN_MODE_SHARE        (1)        Extra = Not used
OPEN_MODE_BYHANDLE (2)        Extra = Handle
OPEN_MODE_ASPARALLEL (16)        Extra = Not used
Extra is extra information passed to the OpenEx() function as needed. See the Mode parameter.
 

Remarks
Opens a port for doing input and output.

OPEN_MODE_NORMAL         Same as Open().
OPEN_MODE_SHARE            Opens the port in a shared mode. This allows the port to be opened and used even if another applicaion/driver is using this port.  This is most useful when using Win NT.
OPEN_MODE_BYHANDLE     This allows the application writer to open the port and pass the handle to the I/O control.
OPEN_MODE_ASPARALLEL     This opens the port as a parallel port.  This is useful if a parallel port is opened with a non-standard parallel port name. (i.e. "\\.\LPT2USB1:").
Returns
1 if successful and 0 if the function fails.
2 if successful but the port setup fails can happen when another app/device driver is using the port.
 

Example
Result = IO1.Open("LPT1:", "", OPEN_MODE_SHARE, 0) 'Open a parallel Port. In shared mode.

NOTE: On Win NT Open() can fail if another device/driver is setup to use the port you are trying to open. Remove all devices/drivers setup to use this port, including printer drivers. Note: IODef.bas has VB constants for the IO control (in the samples directory)
 

  CancelIO(CancelFlags)
 

          Parameters

CancelFlags Determines how and what cancel action is taken.  These values can be added or ORed to combine the flags.
CANCEL_TXABORT    (1)     Abort the pending/current writes to the comm port.
CANCEL_RXABORT    (2)    Abort the pending/current reads from the comm port.
CANCEL_TXCLEAR     (4)    Purge the transmit queue.
CANCEL_RXCLEAR     (8)    Purge the receive buffer.
          Remarks
Cancels pending reads or writes to the open port, also can purge/remove any information in the read or write buffers.  Canceling pending I/O works best if using the background I/O Mode.
          Returns
          1 if successful and a 0 if the function fails.

          Example
          Result = IO1.CancelIO(1+2+4+8) 'Cancels pending I/O.

Note: IODef.bas has VB constants for the IO control (in the samples directory)

 
    GetInfoInt(InfoID)
 

          Parameters

InfoID A number that determines what information is returned by the function.
INFO_BAUD (01)      retuns the baud rate
          Remarks
Returns information about the opened communications channel.

Returns

          The requested data.

          Example
          Result = IO1.GetInfoInt(1) '.

Note: IODef.bas has VB constants for the IO control (in the samples directory)
  GetInfoString(InfoID)
 

          Parameters

InfoID A number that determines what information is returned by the function.
INFO_BAUD (01)      retuns the baud rate
INFO_PORT (02)       returns the port name
INFO_SETUP (03)    return the setup string
          Remarks
Returns information about the opened communications channel.

Returns

          The requested data.

          Example
          Result = IO1.GetInfoString(1) '.

Note: IODef.bas has VB constants for the IO control (in the samples directory)
WriteBytes(Data)
 
Parameters
Data is a byte array.

Remarks
The array must be a byte array with a single dimension.

Returns
Returns number of bytes actually written.

Example
Dim darray(2) As Byte

darray(0) = 111
darray(1) = 112
darray(2) = 113
IO1.WriteBytes (darray)


 

ReadBytes(Data, Length)
 
 

Parameters
Data  is a byte array.
Length  is the number of character to read into the byte array.

Remarks
The actual length of bytes read will not exceed the length of the array.  The array must be a byte array with a single dimension.

Returns
Returns number of bytes actually written.

Example
Dim darray(3) As Byte

res = IO1.ReadBytes(darray, 4)
res = darray(0)
res = darray(1)
res = darray(2)
res = darray(3)
 


 
 

Status

ParallelStatus (Property) R

 
Remarks
This reflects the current status of the parallel/printer port as follows:

Example:
IOStatus = IO1.ParallelStatus
If (IOStatus And PARALLEL_SELECTED) Then
NewText = NewText + "Selected. "
Else
NewText = NewText + "Not Selected. "
End If

OR

IOStatus = IO1.ParallelStatus
If (IOStatus And &h80) Then
NewText = NewText + "Selected. "
Else
NewText = NewText + "Not Selected. "
End If

Note: IODef.bas has VB constants for the IO control (in the samples directory)


 
PARALLEL_PAPER_EMPTY 

PARALLEL_OFF_LINE 

PARALLEL_POWER_OFF 

PARALLEL_NOT_CONNECTED 

PARALLEL_BUSY 

PARALLEL_SELECTED 

0x4

0x8

0x10

0x20

0x40

0x80


 
 
 
 

SerialStatus (Property) R

 
Remarks
This reflects the current status of the serial port as follows:

Example:
IOStatus = IO1.SerialStatus
If (IOStatus And SERIAL_RXEMPTY) Then
NewText = NewText + "RX Buffer Empty, "
else
NewText = NewText + "RX Buffer Not Empty, "
End If

OR

IOStatus = IO1.SerialStatus
If (IOStatus And &h40) Then
NewText = NewText + "RX Buffer Empty, "
else
NewText = NewText + "RX Buffer Not Empty, "
End If

Note: IODef.bas has VB constants for the IO control (in the samples directory)

SERIAL_RXOVER 

SERIAL_OVERRUN 

SERIAL_RXPARITY 

SERIAL_FRAME 

SERIAL_BREAK

SERIAL_TXFULL

SERIAL_TXEMPTY 

SERIAL_RXEMPTY 

SERIAL_CTS_TXHOLD

SERIAL_DSR_TXHOLD 

SERIAL_RLSD_TXHOLD

SERIAL_XOFF_TXHOLD 
 
 

SERIAL_CTS_ON 

SERIAL_DSR_ON 

SERIAL_RING_ON 

SERIAL_RLSD_ON 

0x0001

0x0002 

0x0004 

0x0008 

0x0010 

0x0100

0x0020 

0x0040 

0x0200

0x0400

0x0800

0x1000
 
 

0x010000

0x020000

0x040000

0x080000

An input buffer overflow has occurred. There is either no room in the input buffer, or a character was received after the end-of-file (EOF) character.

A character-buffer overrun has occurred. The next character is lost.

The hardware detected a parity error.

The hardware detected a framing error.

The hardware detected a break condition.

The application tried to transmit a character, but the output buffer was full.

The transmit buffer is empty.

The receive buffer is empty.

Transmission is waiting for the CTS (clear-to-send) signal to be sent.

Transmission is waiting for the DSR (data-set-ready) signal to be sent.

Transmission is waiting for the RLSD (receive-line-signal-detect) signal to be sent.

Transmission is waiting because the XOFF character was received.
 
 

The CTS (clear-to-send) signal is on.

The DSR (data-set-ready) signal is on.

The ring indicator signal is on.

The RLSD (receive-line-signal-detect) signal is on.


 
 
 

TCPStatus (Property) R

 
Remarks
This reflects the current status of the TCP connection as follows:  These values are valid before the TCP connection is established and after the TCP connection is made.

Example:
IOStatus = IO1.TCPStatus
If (IOStatus And &h2) Then
NewText = NewText + "Connection Ready to Transmit"
else
NewText = NewText + "Connection Not Ready to Transmit"
End If

OR

IOStatus = IO1.TCPStatus
If (IOStatus And &h1) Then
NewText = NewText + "Data Present and Ready to Read"
else
NewText = NewText + "No Data Present "
End If

Note: IODef.bas has VB constants for the IO control (in the samples directory)

TCP_READ_READY 

TCP_WRITE_READY 

TCP_LOST_CONNECTION 
 

0x1

0x2

0x4
 


 
 
 
 
 
 

NumCharsInQue (Property) R

 
Remarks
This reflects the number of bytes/characters in the input buffer (waiting to be read).

This value will likely be inaccurate when using a background read operation (i.e. Mode = MODE_ASYNC(2)).  The background read may have already read the data and stored it in an intermediate buffer until the IOCompleteEvent is fired..

NOTE: This value may not function on an NT based OS using a parallel port.
 


 
 

NumCharsOutQue (Property) R

 
Remarks
This reflects the number of bytes/characters in the output buffer (pending write to the port).

This value will likely be inaccurate when using a background write operation(s) (i.e. Mode = MODE_ASYNC(2)).  The background write may not have written the data yet, the data is stored in an intermediate buffer until the pending write is processed.
 


 
 

Events
 
 
 
 
 

IOStatusEvent(StatusType, IOStatus)

 
Parameters
StatusType. Specifies the type of status being reported.

STATUS_TYPE_PARALLEL 1

STATUS_TYPE_SERIAL 2
IOStatus. Specifies the status pertaining to the open port. See the definition of SerialStatusand ParallelStatusfor the value of this parameter.

Remarks

This event is fired whenever a status change is detected on the port. How often status is checked and events are generated is set by StatusEventInterval (default of 250 milliseconds).


 

IOCompleteEvent(JobType, JobId, JobResult)

 
Parameters
JobType. Specifies the type of Job being reported as finished.

BKJOB_WRITE 3

BKJOB_READ 4

JobId. Specifies the Id of the job submitted for background processing.
JobResult. Specifies the result of the job submitted for background processing.

Remarks
This event is fired whenever a background job is finished.  If a read operation is completed, DataBuffer will contain the result of the read operation.
 
 


 
 
 

IOQueueEvent(NumCharsInputQue, NumCharsOutputQue)

 
Parameters
NumCharsInputQue  Reflects the number of characters in the port's input queue/buffer.
NumCharsOutputQue  Reflects the number of characters in the port's output queue/buffer.

Remarks
This event is fired whenever the number of character in either the input or output queue has changed.  This event is provided to allow the application designer to monitor the communications activity.

Example:

If (NumCharsInputQue > 0) Then

TextRead.Text = TextRead.Text + IO1.ReadData(20) End If
NOTE: The value "NumCharsInputQue" may not function on an NT based OS using a parallel port.

 
 

IOPeriodicEvent()

 
Parameters
None

Remarks
This event is fired whenever the StatusEventInterval has expired.  This event is provided to allow the applications designer to add custom communications monitoring on a periodic basis.  This event is enable by setting the property PeriodicEventEnabled to TRUE (1).
 
 


StatusEventInterval (Property) R/W

 
Remarks
Set this to control how often changes in port status are monitored. This affects how often IOStatusEvents, IOQueueEvents, and IOPeriodicEvents are fired and how responsive status events are to changes in port status. If this is set to 0, status events are not fired and the thread monitoring status for status events is terminated until this property is set to non-zero. The units for this property are in milliseconds. The default value is 250 milliseconds.

 
 
 
 
 

PeriodicEventEnabled (Property) R/W

 
Remarks
Set this to enable the IOPeriodicEvent.

 
 
 
 
 

Parallel Specific

InitPrinter(Code)

Parameters
Code Specifies what action to take.
1 assert init signal to device on printer port.
Remarks
Executes a printer reset via the Init pin on the parallel printer port. When asserting a signal, the signal transitions from false to true and back to false.
Returns
1 for success and 0 if the function fails.

Example
ret = IO1.InitPrinter(1)


 

Out (Address, Data)

Parameters
Address. Specifies the address of the port hardware.
Data. Specifies the byte to be written.

Remarks
Because this is used to write a data byte directly to the parallel port hardware, do not call the Open() or Close() functions when using the Out() function..  See below for the address of standard parallel ports.

Port addresses:

          LPT1: 378 Hex(Data), 379 Hex(Status), 37A Hex(Control)

          LPT2: 278 Hex(Data), 279 Hex(Status), 27A Hex(Control)

          LPT3: 3BC Hex(Data), 3BD Hex(Status), 3BE Hex(Control)
 

  In (Address)  
Parameters
Address. Specifies the address of the port hardware.

Remarks
Because this is used to read a data byte directly from the parallel port hardware, do not call the Open() or Close() functions when using the In() function.  See below for the address of standard parallel ports.

Returns
The data byte of the addressed port register.

Port addresses:

          LPT1: 378 Hex(Data), 379 Hex(Status), 37A Hex(Control)

          LPT2: 278 Hex(Data), 279 Hex(Status), 27A Hex(Control)

          LPT3: 3BC Hex(Data), 3BD Hex(Status), 3BE Hex(Control)

Example
Result = IO1.In(&H378)
  Or
Result = IO1.In(&H378) And &Hff 'restores to unsigned byte
 
 

DeviceControl(Command, Data, Buffer) WinNT Only
 
Parameters
Command. Specifies the command.
ASSERT_PAR_CONTROL (1441800) Assert parallel port control signal(s).
Data. Specifies data that the command uses.
PARALLEL_INIT (1)
PARALLEL_AUTOFEED (2)
Buffer. Specifies additional data as needed.

Remarks
Sends a command to port hardware through the port driver.

Returns
The return data is a string.  If the function fails the string is empty.  If the function succeeds the string is non-empty and its contents depend on the command sent. When asserting a signal, the signal transitions from false to true and back to false (pulse).

Example
ret = IO1.DeviceControl(1441800, 1, "")
 


 

Serial Specific
 

SerialPortSetupDialog(PortName)

 
Parameters
PortName Specifies the port name used by the setup dialog.

Remarks
This method displays the serial port setup dialog and allows a user to adjust the port settings.  After the dialog is dismissed by clicking on the "OK" button, the new settings are applied to the currently open port. If no port is open, the settings are saved in the I/O object and can be stored by calling the SerialSetPortDefaults() function.  If the PortName is blank (i.e. ""), the dialog will use the port name of the most recently opened port.
 

Returns
1 for success
0 for fail or cancel button was clicked.

Example

IO1.SerialGetPortDefaults (PortName)    'Get port settings
Result = IO1.SerialPortSetupDialog(PortName)     'Allow user to setup port
If Result = 1 Then
    Result = IO1.SerialSetPortDefaults(PortName, "", -1)       'Save the settings
End If


 
 

SerialSetPortDefaults(PortName, Setup, HSMode)

 
Parameters
PortName Specifies the port to set defaults.
Setup Is a setup string as described in Open()
HSMode Is the handshaking mode, see SetHandshaking()

Remarks
This method allows setting of the default settings of a serial port.  The default settings for a port are maintained/save by the operating system.  If Setup is blank (i.e. ""), this function will use the settings of the last opened port or the settings entered via the SerialPortSetupDialog() function.  If the HSMode is -1, this function will use the settings of the last opened port or the settings entered via the SerialPortSetupDialog() function..  If the PortName is blank (i.e. ""), this function will use the port name of the most recently opened port.  This function will also change/set the settings for the currently opened port (if one is opened).
 

Returns
1 for success or 0 for fail.

                    Example
IO1.SerialPortSetupDialog (PortName)   'Allow user to setup port
Result = IO1.SerialSetPortDefaults(PortName, "", -1)   'Save the settings

 
 
 
 

SerialGetPortDefaults(PortName)

 
Parameters
PortName Specifies the port to get default settings.

Remarks
This method allows retrieval of the default settings of a serial port.  The default setting for a port are maintained/save by the operating system.  If the PortName is blank (i.e. ""), this function will use the port name of the most recently opened port.  This function should be called after the port is opened, as opening of the port will overwrite the setting retrieved by calling this function.

Returns
1 for success or 0 for fail.

                    Example IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1")   'Open port with initial settings
IO1.SerialGetPortDefaults (PortName)     'Get port settings previously stored by SerialSetPortDefaults

 
 
 
 

SerialBreak(BreakMode)

 
Parameters
BreakMode Specifies the state of the serial port break.

Remarks
This method allows the open serial port to be put into a break condition.

Returns
1 for success or 0 for fail.

                    Example
                    IO1.SerialBreak (1)     'Set serial port into a break condition.
                    IO1.Sleep(100)
                    IO1.SerialBreak (0)     'Set serial port into a non-break condition.
 
 
 
 

SerialSetBaud(BaudRate)

 
Parameters
BaudRate Specifies/changes the baud of the serial port.

Remarks
This method allows the open serial port to be put into a break condition.

Returns
1 for success or 0 for fail.

                    Example
                    IO1.SerialSetBaud (9600)     'Set serial baudrate to 9600.
 
 
 
 

Advanced Serial Communications functions

These functions are not typically needed to successfully do serial communication, but are provided to allow advanced control of the serial port. These functions should be called after the SetHandshaking() function is called, as SetHandshaking() will cancel these settings.
 


SerialCTSFlow(Value)

 
Parameters
Value 1 or 0. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether the CTS (clear-to-send) signal is monitored for output flow control. If it is 1 and CTS is low, output is suspended until CTS is high again. The CTS signal is under control of the device (usually a modem/printer), the host simply monitors the status of this signal, the host does not change it. This function should be called before the port is opened.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialCTSFlow(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 


SerialDSRFlow(Value)  
Parameters
Value 1 or 0. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether the DSR (data-set-ready) signal is monitored for output flow control. If this member is 1 and DSR is low, output is suspended until DSR is high again. This signal is under the control of the attached device; the host(PC) only monitors this signal. This function should be called before the port is opened.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialDSRFlow(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 


SerialDTRControl(long Value)  
Parameters
Value 0,1,2,5,6. Controls state of DTR line. Undetermined results if set to other than specified

Remarks
If 0 then the DTR line is lowered when the device is opened.
If 1 then the DTR line is raised when the device is opened.
If set to 2 enables DTR flow-control handshaking.
After the port is opened:
If called with a value of 5 sets DTR high. Only allowed if SerialDTRControl was set to 1 0r 0 before the port was opened.
If called with a value of 6 sets DTR low. Only allowed if SerialDTRControl was set to 1 0r 0 before the port was opened.

Returns
1 if successful or 0 if failed.
Example
Result = IO1.SerialDTRControl(0)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
...
Result = IO1.SerialDTRControl(5)
 
 


SerialDSRSensitivity(Value)  
Parameters
Value 1 or 0. Controls DSR Sensitivity. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether the communications driver is sensitive to the state of the DSR signal. If this is set to a 1, the driver ignores any bytes received, unless the DSR modem input line is high.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialDSRSensitivity(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 


SerialTxContinueOnXoff(Value)
Parameters
Value 1 or 0. Controls Xon/Xoff behavior. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether transmission stops when the input buffer is full and the driver has transmitted the XOFF character. If this is set to a 1, transmission continues after the XOFF character has been sent. If this is set to a 0, transmission does not continue until the input buffer is within SerialXonLim bytes of being empty and the driver has transmitted the XON character.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialTxContinueOnXoff(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 


SerialOutX(Value)  
Parameters
Value 1 or 0. Controls Xon/Xoff behavior. Undetermined results if set to other than 1 or 0

Remarks
Specifies whether XON/XOFF flow control is used during transmission. If this member is a 1, transmission stops when the XOFF character is received and starts again when the XON character is received.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialOutX(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 
 


SerialInX(Value)  
Parameters
Value 1 or 0. Controls Xon/Xoff behavior. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether XON/XOFF flow control is used during reception. If this is set to a 1, the XOFF character is sent when the input buffer comes within a preset limit of bytes of being full (see SerialXonLimit and SerialXoffLimit), and the XON character is sent when the input buffer comes within a preset limit of bytes of being empty.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialInX(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 


SerialErrorReplacment(Value)  
Parameters
Value 1 or 0. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether bytes received with parity errors are replaced with the character specified by the SerialErrorCharacter member function. If this is set to a 1 and the Parity is set to a 1, replacement occurs.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialErrorReplacment(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 


SerialNullStripping(Value)  
Parameters
Value 1 or 0. Undetermined results if set to other than 1 or 0.

Remarks
Specifies whether null bytes are discarded. If this is set to 1, null bytes are discarded when received.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialNullStripping(1)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 
 
 


SerialRTSControl(Value)  
Parameters
Value 0,1,2,3,5,6. Controls state of RTS line. Undetermined results if set to other than specified

Remarks
If 0 then the RTS line is lowered when the device is opened.
If 1 then the RTS line is raised when the device is opened.
If set to 2 enables RTS flow-control handshaking. The driver raises the RTS line, enabling the attached device to send (when the input buffer has enough room to receive data). The driver lowers the RTS line, preventing the attached device from sending (when the input buffer does not have enough room to receive data).
If set to 3 specifies that the RTS line will be high if bytes are available for transmission. After all buffered bytes have been sent, the RTS line will be low. (Not supported on Win95)
After the port is opened:
If called with a value of 5 sets RTS high. Only allowed if SerialRTSControl was set to 1 0r 0 before the port was opened.
If called with a value of 6 sets RTS low. Only allowed if SerialRTSControl was set to 1 0r 0 before the port was opened.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialRTSControl(0)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
...
Result = IO1.SerialRTSControl(5)
 
 
 
 
 


SerialXonLimit(Value)  
Parameters
Value Xon Limit.

Remarks
Specifies the minimum number of bytes allowed in the input buffer before the XON character is sent.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialXonLimit(256)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 
 


SerialXoffLimit(Value)  
Parameters
Value Xoff Limit.

Remarks
Specifies the maximum number of bytes allowed in the input buffer before the XOFF character is sent.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialXoffLimit(100)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 
 
 


SerialXonCharacter(Value)

 
Parameters
Value Xon character.

Remarks
Specifies the Xon character.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialXonCharacter(17)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 


SerialXoffCharacter(Value)  
Parameters
Value Xoff character.

Remarks
Specifies the Xoff character.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialXoffCharacter(19)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 
 


SerialErrorCharacter(Value)  
Parameters
Value Error character.

Remarks
Specifies the Error character, the character used to replace bytes received with a parity error.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialErrorCharacter('?')
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 
 
 


SerialEndCharacter(Value)  
Parameters
Value End character.

Remarks
Specifies the End character, the character used to signal the end of data.

Returns
1 if successful or 0 if failed.

Example
Result = IO1.SerialEndCharacter(&hFF)
...
Result = IO1.Open("COM2:", "baud=9600 parity=N data=8 stop=1") 'Open a serial Port.
 


 
 
 

Home Page | Site Map | Copyright (c) 1998 by JSPayne of Cortland NY